RoHS Compliant Made in USA

Scope:

Stranded copper conductors (ASTM B-8), crosslinked polyethylene (type XHHW-2) insulated for moisture and heat resistance. Phase identified and cabled together with fillers and/or binders as required. Cabled core is covered with an overall black PVC jacket that is gas and oil resistant. Jacket available in colors. Suitable for use in hazardous locations: Class 1 and 2, Division 2.

Applicable Standards and Tests:

  • UL 1277 at 600 volts
  • Flame Rated: IEEE 1202 (70,000 BTU)
  • ICEA S-95-658/NEMA WC-70
  • Temperature Rated at 90°C Wet/Dry
  • -25°C Rated
  • VW-1 Rated Conductors
  • Direct Burial & Sunlight Resistant
  • Exposed Runs Rated (TC-ER)
  • Color Code: NEMA WC 57/ICEA S-73-532 Table E-1 or E-2

Print Wheel:

Kris-Tech Wire XX AWG XX conductor E515926 (UL) TC-ER XHHW-2 600V 90°c wet/dry PVC jacket sun res FT4 oil res I DIR BUR “RoHS” made in USA

Construction:

Conductors:

Concentric 19 strand soft drawn annealed copper per UL and ASTM requirements. Tinned conductors and other stranded configurations are available upon request. Single conductors are Oil & Gas Resistant I.

Insulation:

Crosslinked polyethylene (XLP) is VW-1 rated and Oil and Gasoline Resistant I. All black insulation is rated “Sunlight Resistant”.

Jacket:

A black, flame resistant, Polyvinyl Chloride (PVC) jacket is extruded over the assembly. The surface profile shall approximate that of the interior assembly.

Identification and Packaging:

The wire shall be identified by surface marking indicating the manufacturer, conductor size, voltage rating, UL symbol, and type designation. Custom lengths, color, and packaging is available by request.

AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
142450.3656
143450.4182
144450.43102
145450.47122
147450.51161
149600.63218
1410600.70238
1412600.70279
1416600.78389
1419600.82438
1432801.072777
AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
122450.4076
123450.43111
124450.48141
125450.52167
127600.60242
129600.70302
1210600.78331
1212600.78389
1216800.91544
1219800.96620
AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
102450.45103
103450.48154
104450.52214
105600.61256
107600.66344
109600.78431
1010800.91475
1012800.91592