RoHS Compliant Made in USA

Scope:

Stranded copper conductors (ASTM B-8), polyvinyl chloride (PVC) insulated, jacketed in nylon for moisture and heat resistance. Phase identified and cabled together with fillers and/or binders as required. Optional bare copper or insulated green ground cable is included as well. Cabled core is covered with an overall black PVC jacket that is gas and oil resistant. Jacket available in colors. Suitable for use in hazardous locations: Class 1 and 2, Division 2.

Applicable Standards and Tests:

  • UL 1277 at 600 volts
  • Flame Rated: IEEE 1202 (70,000 BTU)
  • ICEA S-95-658/NEMA WC-70
  • Temperature Rated at 90°C Wet/Dry
  • -25°C Rated
  • Direct Burial & Sunlight Resistant
  • Exposed Runs Rated (TC-ER)
  • Color Code: NEMA WC 57/ICEA S-73-532 Table E-1, E-2, or M4

Construction:

Conductors:

Concentric 19 strand soft drawn annealed copper per UL and ASTM requirements. Sizes #4 AWG and larger are a concentric 7 strand soft drawn annealed copper per UL and ASTM requirements. Tinned conductors and other stranded configurations are available upon request. Single conductors are Oil & Gas Resistant II.

Insulation:

Concentrically applied PVC insulation with a Nylon jacket. Rated at 90°C dry and 75°C wet.

Ground Conductor:

Bare copper conductor or insulated green polyvinyl chloride (PVC) insulated, jacketed in nylon.

Jacket:

A black, flame resistant, Polyvinyl Chloride (PVC) jacket is extruded over the assembly. The surface profile shall approximate that of the interior assembly.

Identification and Packaging:

The wire shall be identified by surface marking indicating the manufacturer, conductor size, voltage rating, UL symbol, and type designation. Custom lengths, color, and packaging is available by request.

Print Wheel:

Kris-Tech Wire XX AWG XX conductor E515926 (UL) TC-ER THHN 600V 90°c wet/dry PVC jacket sun res FT4 “RoHS” made in USA

VNTC Tray Cable with NO Ground

AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
82450.43177
83600.57283
84600.63355
62600.56281
63600.70400
64600.77515
42600.66406
43800.87627
44800.95787
22600.76611
23801.00965

VNTC Tray Cable with Bare Copper Ground

AWGNumber of ConductorsSize of Ground Wire (AWG)Jacket Thickness (mils)Nominal Diameter over Jacket (inches)Approximate Net Weight (Lbs./Mft.)
12212450.3598
12312450.39136
10210450.40155
10310450.45198
8210450.48213
8310600.57313
628600.61338
638600.70459
428600.69475
438600.80636
226600.81698
236800.971042

VNTC Tray Cable with Green Insulated Ground

AWGNumber of ConductorsSize of Ground Wire (AWG)Jacket Thickness (mils)Nominal Diameter over Jacket (inches)Approximate Net Weight (Lba./Mft.)
12212450.38105
12312450.42142
10210450.44164
10310450.48207
8210450.51222
8310600.60323
628600.66357
638600.74478
428600.74494
438800.88686
226 800.91755