Single conductor polyvinylchloride (PVC) insulated, 600-volt, type UF. This product is suitable for continuous service in direct burial, wet and dry locations, 60°C and 600 volts. This product complies with EU Directive 2002/95/EC known as ROHS.
The single copper conductors shall be solid or stranded annealed or hard uncoated copper per UL83 and ASTM requirements.
Concentrically applied Polyvinylchloride (PVC) insulation in accordance with UL83. The minimum at any point shall not be less than 90% of the specified average thickness in compliance with UL 493.
The wire shall be identified by surface marking indicating the manufacturer, conductor size, voltage rating, UL symbol, and type designation. 500 and 2500 ft. spools are standard, custom lengths, color, and packaging is available by request.
Kris-Tech Wire Co. E-96620 (UL) type UF 12/1 600 volts
AWG | Standard Number of Strands | Insulation Thickness (mils) | Nominal Diameter | Approx. Net Weight (Lbs/Mft) |
---|---|---|---|---|
14 | Solid or 7 | 60 | 0.19/0.20 | 26/27 |
12 | Solid or 7 | 60 | 0.20/0.21 | 35/37 |
10 | Solid or 7 | 60 | 0.22/0.24 | 50/51 |
8 | Solid or 7 | 80 | 0.29/0.31 | 85/89 |
6 | 7 | 80 | 0.35 | 119 |
4 | 7 | 80 | 0.39 | 174 |
2 | 7 | 80 | 0.45 | 258 |
1 | 19 | 95 | 0.52 | 331 |
1/0 | 19 | 95 | 0.56 | 406 |
2/0 | 19 | 95 | 0.61 | 510 |
3/0 | 19 | 95 | 0.66 | 624 |
4/0 | 19 | 95 | 0.72 | 772 |