RoHS Compliant Made in USA

Scope:

Single conductor PVC (polyvinyl chloride) insulated, 600-volt dual rated TW/THW. Suitable for power, grounding, and lighting in residential, commercial and industrial applications.

Applicable Standards and Tests:

ASTM B-1, B-3, B-8, and B-33, UL 83, NEC 310, NFPA 70, and the California Department of Transportation (CALTRANS). All products are spark tested at 7500 VAC unless otherwise specified.

Construction:

Conductors:

The single conductors are solid or stranded annealed, coated or bare copper.

Insulation:

Concentrically applied PVC insulation rated at -25°C to 75°C, wet or dry locations.

Identification and Packaging:

The wire shall be identified by surface marking indicating the manufacturer, AWG size, voltage rating, UL symbol, temperature rating of 75°C and type designation. 500 ft/spl.packed 4/box or 2500 feet/spl spools are standard. Custom lengths are available by request.

Print Wheel:

Kris-Tech Wire Co. #XX AWG type TW or THW 75C 600V (UL)

Value Add Service:

  • Custom lengths and put-ups
  • 12 available colors
  • Wire paralleling and cabling
  • Wire striping
  • Custom print legends and labels
AWGNumber of StrandsInsulation (mils.)Alternative Insulation (mils)Nominal Overall Diameter - Inches (standard strands)Approx. Shipping Weight (Lbs/Mft)
14Solid or 730450.13"/0.14" 18/19
12Solid or 730450.14"/0.16"28/29
10Solid or 730450.17"/0.18"41/29
8Solid or 745600.22"/0.24"72/74
6Solid or 760-0.28"/0.31"105/107
47 or 13360-0.35"/0.39"160/167
27 or 13360-0.41"/0.45"250/265
11980-0.49"324
1/01980-0.53"398
2/01980-0.58"496
3/01980-0.63"611
4/01980-0.69"755
250 MCM3795-0.77"770
300 MCM3795-0.82"923
350 MCM3795-0.87"1083
400 MCM3795-0.95"1235
500 MCM3795-1.00"1573