RoHS Compliant Made in USA

Scope:

Stranded copper conductors (ASTM B-8), polyvinyl chloride (PVC) insulated, jacketed in nylon for moisture and heat resistance. Phase identified and cabled together with fillers and/or binders as required. Optional bare copper or insulated green ground cable is included as well. Cabled core is covered with an Aluminum-Mylar shield and a tinned copper drain wire, covered with overall black PVC jacket that is gas and oil resistant. Jacket available in colors. Suitable for use in hazardous locations: Class 1 and 2, Division 2.

Applicable Standards and Tests:

  • UL 1277 at 600 volts
  • Flame Rated: IEEE 1202 (70,000 BTU)
  • ICEA S-95-658/NEMA WC-70
  • Temperature Rated at 90°C Wet/Dry
  • -25°C Rated
  • Direct Burial & Sunlight Resistant
  • Exposed Runs Rated (TC-ER)
  • Color Code: NEMA WC 57/ICEA S-73-532 Table E-1, E-2, or M4

Construction:

Conductors:

Concentric 19 strand soft drawn annealed copper per UL and ASTM requirements. Sizes #4 AWG and larger are a concentric 7 strand soft drawn annealed copper per UL and ASTM requirements. Tinned conductors and other stranded configurations are available upon request. Single Conductors are Oil & Gas Resistant I.

Insulation:

Concentrically applied PVC insulation with a Nylon jacket. Rated at 90°C dry and 75°C wet.

Ground Conductor:

Bare copper conductor or insulated green polyvinyl chloride (PVC) insulated, jacketed in nylon.

Shield:

Aluminum-Mylar shield with a tinned copper drain wire.

Jacket:

A black, flame resistant, Polyvinyl Chloride (PVC) jacket is extruded over the assembly. The surface profile shall approximate that of the interior assembly.

Identification and Packaging:

The wire shall be identified by surface marking indicating the manufacturer, conductor size, voltage rating, UL symbol, and type designation. Custom lengths, color, and packaging is available by request.

Print Wheel:

Kris-Tech Wire XX AWG XX conductor E515926 (UL) shielded TC-ER THHN 600V 90°c wet/dry PVC jacket sun res FT4 “RoHS” made in USA

VNTC Tray Cable Shielded with NO Ground

AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
82450.43190
83600.57283
84600.63355
62600.56294
63600.70400
64600.77515
42600.66421
43800.87627
44800.95787
22600.76627
23801.00967

VNTC Tray Cable Shielded with Bare Copper Ground

AWGNumber of ConductorsSize of Ground Wire (AWG)Jacket Thickness (mils)Nominal Diameter over Jacket (inches)Approximate Net Weight (Lbs./Mft.)
12212450.35111
12312450.39136
10210450.40167
10310450.45198
8210450.48226
8310600.57313
628600.61354
638600.70459
428600.69490
438600.80636
226600.81720
236800.971042

VNTC Tray Cable Shielded with Green Insulated Ground

AWGNumber of ConductorsSize of Ground Wire (AWG)Jacket Thickness (mils)Nominal Diameter over Jacket (inches)Approximate Net Weight (Lba./Mft.)
12212450.38105
12312450.42142
10210450.44164
10310450.48207
8210450.51222
8310600.60323
628600.66357
638600.74478
428600.74494
438800.88686
226800.91755