Stranded copper conductors (ASTM B-8), polyvinyl chloride (PVC) insulated, jacketed in nylon for moisture and heat resistance. Phase identified and cabled together with fillers and/or binders as required. Optional bare copper or insulated green ground cable is included as well. Cabled core is covered with an overall black PVC jacket that is gas and oil resistant. Jacket available in colors. Suitable for use in hazardous locations: Class 1 and 2, Division 2.
Concentric 19 strand soft drawn annealed copper per UL and ASTM requirements. Sizes #4 AWG and larger are a concentric 7 strand soft drawn annealed copper per UL and ASTM requirements. Tinned conductors and other stranded configurations are available upon request. Single conductors are Oil & Gas Resistant II.
Concentrically applied PVC insulation with a Nylon jacket. Rated at 90°C dry and 75°C wet.
Bare copper conductor or insulated green polyvinyl chloride (PVC) insulated, jacketed in nylon.
A black, flame resistant, Polyvinyl Chloride (PVC) jacket is extruded over the assembly. The surface profile shall approximate that of the interior assembly.
The wire shall be identified by surface marking indicating the manufacturer, conductor size, voltage rating, UL symbol, and type designation. Custom lengths, color, and packaging is available by request.
Kris-Tech Wire XX AWG XX conductor E515926 (UL) TC-ER THHN 600V 90°c wet/dry PVC jacket sun res FT4 “RoHS” made in USA
AWG | Number of Conductors | Jacket Thickness (mils) | Nominal Diameter over Jacket (inches) | Approx. Net Weight (Lbs/Mft) |
---|---|---|---|---|
8 | 2 | 45 | 0.43 | 177 |
8 | 3 | 60 | 0.57 | 283 |
8 | 4 | 60 | 0.63 | 355 |
6 | 2 | 60 | 0.56 | 281 |
6 | 3 | 60 | 0.70 | 400 |
6 | 4 | 60 | 0.77 | 515 |
4 | 2 | 60 | 0.66 | 406 |
4 | 3 | 80 | 0.87 | 627 |
4 | 4 | 80 | 0.95 | 787 |
2 | 2 | 60 | 0.76 | 611 |
2 | 3 | 80 | 1.00 | 965 |
AWG | Number of Conductors | Size of Ground Wire (AWG) | Jacket Thickness (mils) | Nominal Diameter over Jacket (inches) | Approximate Net Weight (Lbs./Mft.) |
---|---|---|---|---|---|
12 | 2 | 12 | 45 | 0.35 | 98 |
12 | 3 | 12 | 45 | 0.39 | 136 |
10 | 2 | 10 | 45 | 0.40 | 155 |
10 | 3 | 10 | 45 | 0.45 | 198 |
8 | 2 | 10 | 45 | 0.48 | 213 |
8 | 3 | 10 | 60 | 0.57 | 313 |
6 | 2 | 8 | 60 | 0.61 | 338 |
6 | 3 | 8 | 60 | 0.70 | 459 |
4 | 2 | 8 | 60 | 0.69 | 475 |
4 | 3 | 8 | 60 | 0.80 | 636 |
2 | 2 | 6 | 60 | 0.81 | 698 |
2 | 3 | 6 | 80 | 0.97 | 1042 |
AWG | Number of Conductors | Size of Ground Wire (AWG) | Jacket Thickness (mils) | Nominal Diameter over Jacket (inches) | Approximate Net Weight (Lba./Mft.) |
---|---|---|---|---|---|
12 | 2 | 12 | 45 | 0.38 | 105 |
12 | 3 | 12 | 45 | 0.42 | 142 |
10 | 2 | 10 | 45 | 0.44 | 164 |
10 | 3 | 10 | 45 | 0.48 | 207 |
8 | 2 | 10 | 45 | 0.51 | 222 |
8 | 3 | 10 | 60 | 0.60 | 323 |
6 | 2 | 8 | 60 | 0.66 | 357 |
6 | 3 | 8 | 60 | 0.74 | 478 |
4 | 2 | 8 | 60 | 0.74 | 494 |
4 | 3 | 8 | 80 | 0.88 | 686 |
2 | 2 | 6 | 80 | 0.91 | 755 |