RoHS Compliant Made in USA

Scope:

Stranded copper conductors (ASTM B-8), polyvinyl chloride (PVC) insulated, jacketed in nylon for moisture and heat resistance. Phase identified and cabled together with fillers and/or binders as required. Cabled core is covered with an Aluminum-Mylar shield and a tinned copper drain wire, covered with overall black PVC jacket that is gas and oil resistant. Jacket available in colors. Suitable for use in hazardous locations: Class 1 and 2, Division 2.

Applicable Standards and Tests:

  • UL 1277 at 600 volts
  • Flame Rated: IEEE 1202 (70,000 BTU)
  • ICEA S-95-658/NEMA WC-70
  • Temperature Rated at 90°C Wet/Dry
  • -25°C Rated
  • Direct Burial & Sunlight Resistant Jacket
  • Exposed Runs Rated (TC-ER)
  • Color Code: NEMA WC 57/ICEA S-73-532 Table E-1 or E-2

Construction:

Conductors:

Concentric 19 strand soft drawn annealed copper per UL and ASTM requirements. Tinned conductors and other stranded configurations are available upon request. Single Conductors are Oil & Gas Resistant I.

Insulation:

Concentrically applied PVC insulation with a Nylon jacket. Rated at 90°C dry and 75°C wet. 16-18 AWG TFFN wire only, 10-14 AWG THHN only.

Shield:

Aluminum-Mylar shield with a tinned copper drain wire.

Jacket:

A black, flame resistant, Polyvinyl Chloride (PVC) jacket is extruded over the assembly. The surface profile shall approximate that of the interior assembly. An optional rip cord can be inserted underneath the jacket for assisted stripping.

Identification and Packaging:

The wire shall be identified by surface marking indicating the manufacturer, conductor size, voltage rating, UL symbol, and type designation. Custom lengths, color, and packaging is available by request.

Print Wheel:

Kris-Tech Wire XX AWG XX conductor E515926 (UL) shielded TC-ER THHN 600V 90°c wet/dry PVC jacket sun res FT4 oil res I DIR BUR “RoHS” made in USA

Value Add Service:

  • Custom lengths and put-ups
  • 12 available colors
  • Wire paralleling and cabling
  • Wire striping
  • Custom print legends and labels
AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
182450.2652
183450.2762
184450.3072
185450.3283
187450.35101
189450.40127
1810450.44139
1812450.44128
1816450.52242
1819600.55251
1825600.64302
AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
162450.2964
163450.3080
164450.3394
165450.36109
167450.39132
169450.45162
1610600.54178
1612600.54220
1616600.59291
1619600.62316
1625600.73404
AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
142450.3280
143450.34102
144450.37122
145450.40144
147450.43180
149600.54241
1410600.59257
1412600.59302
1416600.66428
1419600.69433
1425600.82554
AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
122450.3693
123450.38128
124450.42160
125450.45195
127600.54243
129600.61324
1210600.68347
1212600.68408
1216600.75579
1219600.80606
1225800.99820
AWGNumber of ConductorsJacket Thickness (mils)Nominal Diameter over Jacket (inches)Approx. Net Weight (Lbs/Mft)
102450.42133
103450.44182
104450.50227
105600.55284
107600.60370
109600.71463
1010600.79515
1012600.79604
1016800.92845